( ... items )

FIELData Industrial

Ud. está en: Inicio » Productos » Catálogo de Productos » TEMPERATURA » Transmisores-Temperatura »

Transmisor de Temperatura TT421

The Digital Temperature Transmitter TT421 is the cost effective solution for temperature measurement and control dedicated for head mounting.
  • Detalles de Productos
  • Pregunta sobre este artículo

TRANSMISOR DE TEMPERATURA TT421

alt
APLICACION MODELO TECNOLOGIA MARCA
Temperatura TT421 HART - 4 a 20 mA Smar
FUNCION CODIGO SECCION
Transmisor de Temperatura TT421.

PRODUCTOS EN STOCK

TRANSMISOR DE TEMPERATURA PARA CABEZAL MOD. TT421
08-1006 08

TT421
Head Mount Smart Temperature Transmitter 4 to 20 mA + HART.

The Digital Temperature Transmitter TT421 is the cost effective solution for temperature measurement and control dedicated for head mounting.

The Smar TT421 is a powerful and extremely versatile programmable temperature transmitter, which can be used with practically all relevant temperature sensors as well as with load cells, resistance position indicators, etc.

A same unit can be used for different measuring ranges and many types of sensors reducing drastically calibration and maintenance time.

Complete configuration is possible using PC software interface (CONF401) or via Hand-Held (HPC301). Configured to customer specs, prior to shipping.

. alt


Some Characteristics:

Output
Signal Two-wire, 4-20 mA with HART superimposed digital communication protocol Version 5.1.
Output current according to NAMUR-NE43.
Power Supply 12-45 Vdc

Input
Single unit accepts signal from:

  • Thermocouples, RTD's and Differential RTD's
  • mV signals from radiation pyrometers, load cells, etc
  • Ohm signals from position indicators, etc


Isolation Factory tested isolation for 1500V
Accuracy ±0.02 % basic accuracy

Measured Types

  • Single sensor: 2, 3, or 4 wire configurations
  • Dual Sensor - Differential - Average - Maximum - Minimum


Configuration Complete configuration is possible using PC software interface or via Hand-Held
Calibration With applied reference and without reference.
Access Protection Yes, via passwords
Diagnostics Yes, via communication.
Control Block Yes, via PID function.
Setpoint Generator function Yes, ideal for batch processes.

Alarms

  • Dual, trip levels adjustable over entire range.
  • High or Low action.
  • Acknowledge, messaging


Linearization Linearization international standards and custom calibration according to Callendar Van Dusen
Temperature Limits Ambient: -40 to 75 ºC (-40 to 167 ºF)
Humidity Limits 10 to 100% RH
Mounting Mounts in industry standard DIN Form B connection head.