MANOMETRO ESTANDAR TIPO CAPSULA PARA PRESION DIFERENCIAL

alt
APLICACION MODELO TECNOLOGIA MARCA
Presión KP63Dif,D9/ 100Dif,D4/ 160Dif,D4 Neumática AFRISO
FUNCION CODIGO SECCION
Manómetro estandar tipo cápsula para presión diferencial 01-2001 01

Standard capsule type pressure gauges for differential pressure.

Application.

For differential pressure measurement of gaseous, dry media which are non-corrosive. Especially suitable for filter loss measurement in air conditioning and ventilation applications. When measuring gas or vapour, the instruments must be used in accordance with the safety recommendations of EN 837-2.

Type D 9/D 4
Nominal size 63 – 100 – 160
Function
The "plus" pressure (= high pressure) is applied to the inside of the diaphragm.
The "minus" pressure (= low pressure) is applied to the inside of the pressure tight housing. The pressure difference causes the diaphragm to change its shape, thus generating the movement required to measure the pressure. This displacement is picked up by the movement. The differential pressure is directly indicated by the pointer of the gauge.
Accuracy class (EN 837-3/6) 1.6
Ranges (EN 837-3/5)
NG 63 0/16 to 0/400 mbar
NG 100 0/ 6 to 0/400 mbar
NG 160 0/ 4 to 0/400 mbar

.

alt


Application area
Static load: full scale value
Dynamic load: 0.9 x full scale value
Overpressure safety full scale value
Maximum static pressure 400 mbar

Operating temperature range
Medium: Tmax = +60 °C
Ambient: Tmin = -20 °C
Tmax = +60 °C

Temperature performance
Indication error when the temperature of the measuring element deviates from 20 °C: rising temp. approx. ±0.6 %/10K falling temp. approx. ±0.6 %/10K percentage of full scale value

Protection IP 66 (EN 60529)

Standard version

Connection (wetted parts) NG 63: 2 x G1/4B – spanner size 14 centre back (brass) NG 100: 2 x G1/2B – spanner size 22 bottom (stainless steel) 2 x G1/2B – spanner size 22 centre back (brass) (EN 837-3/7.3)
Measuring element (wetted part) Capsule element, CuBe alloy
Movement (wetted part)
Brass Seal (wetted part) "Perbunan" nitrile rubber
Dial (wetted part) Aluminium, white. Dial marking black
Pointer (wetted part) Aluminium, black
Housing (wetted part) Stainless steel 304
Bayonet type bezel/crimped bezel Stainless steel 304
Front glass (wetted part) Plastic (PMMA)
Mounting Wall mounting via back flange or 3-hole fixing, panel mounting bezel (each as option). Direct mounting to rigid measuring pipe possible.