Engineering Specification

THE IN-LINE FLOW RATE MONITOR/ TRANSMITTER SHALL:

  • Be factory calibrated for 4-20mA, 0-5Vdc, 1-5Vdc, and square wave pulse outputs.
  • Use the variable annular orifice technique with compression spring recoil.
  • Not require inlet or outlet straight plumbing, or require vertical orientation.
  • Have a measuring accuracy of ±2.5% of full scale in the center third of the measuring range, and ±4% in upper and lower thirds.
  • Have a stainless steel sharp-edged orifice
  • Have a maximum working pressure rating of 3500 or 6000 PSIG for liquids.
  • Have a maximum working pressure rating of 600 or 1000 PSIG for gasses.
  • Have a weather-tight external construction.
. alt


SIMPLE TO INSTALL
All transmitters are factory calibrated and ship fully assembled. Simply install the transmitter into your system and apply power.

INDUSTRY STANDARD OUTPUTS
Transmitters provide proportional analog outputs of 4-20mA, 0-5 Vdc and 1-5 Vdc*, 20-2000 Hz square-wave pulse. These outputs will drive popular data acquisition devices, meters and analog input cards.

DIRECT READING
All transmitters provide a visual indication of flow rate integral to the transmitted output.

WEATHER-TIGHT CONSTRUCTION
The rugged cast aluminum NEMA type 4X enclosure allows installation in outdoor applications and in environments where liquid tight seals are required.

RUGGED AND RELIABLE
Without delicate internal components to break, abrade or corrode, the Lake flow transmitter will provide many years of low-maintenance service.

COMPATIBLE WITH LAKE’S R/T100 AND R100 FLOW ANALYZERS
The Lake flow rate transmitter combines with these Lake analyzers to make a powerful flow instrument capable of remote monitoring of rate and total flows.

*The 1-5Vdc output requires an external 249 ohm resistor (not included with transmitter) to be wired at the receiving device.