The sensor of the probe is based on the principle of solid electrolytes (zirconium dioxide). The free oxygen ion movement begins at temperatures of more 500 °C (solid electrolyte potentiometric method).
  • Detalles de Productos
  • Pregunta sobre este artículo

ANALIZADOR DE OXIGENO VERSION ALTA TEMPERATURA

alt
APLICACION MODELO TECNOLOGIA MARCA
Analítica Oxystem 1800   Afriso
FUNCION CODIGO SECCION
Analizador de oxigeno version alta temperatura. 10-2005 10

Oxygen analyser Oxystem 1800 High temperature version.

Application
Combustion control and control of the furnace atmosphere at high temperatures in furnaces used in the ceramics and aluminium manufacturing industries. Measurements taken directly in the gas with short response times.

Description:
The sensor of the probe is based on the principle of solid electrolytes (zirconium dioxide). The free oxygen ion movement begins at temperatures of more 500 °C (solid electrolyte potentiometric method). The probe is heated by the gas atmosphere, it does not have its own heating. The oxygen concentration is calculated from the cell voltage and the temperature according to Nernst´s law.
The analyser consists of two components, the probe and the evaluation unit. The probe is mounted either horizontally or vertically (at temperatures of more than 1,200 °C). The evaluation unit and the probe are connected by a 2-core screened cable and a screened thermo compensation wire, type S (Pt/PtRh10). The maximum length is 20 m.
Operation via keypad and display. The display shows the current oxygen concentration in percent or ppm and the temperature of the measuring cell. The ranges automatically switch from % by vol. to ppm and to e xx % by vol. O2.

. alt


Technical specifications:

Probe

Operating temperature range
Medium: +700/+1,450 °C
Ambient: -15/ +70 °C

Permissible reference throughput Not required, in special cases 0.5 to 5 l/h
Supply voltage AC 42 V
Power consumption 160 VA
Dimensions (Ø x L) 25 x 600 mm, other lengths on request
Protection IP 55 (EN 60529)
Weight 2.5 kg

Evaluation unit

Operating temperature range Ambient: 5/50 °C
Display 4-line alphanumerical LCD display (temperature, oxygen concentration % by vol.). Range can be selected as required between 21 % by volume and 0.1 ppm O2. Operation via keypad and menus.
Supply voltage AC 110–230 V, 50–60 Hz
Power consumption 20 VA continuous operation
Analogue output 0–20 mA oder 4–20 mA (selectable)
Relay outputs Relay contacts: 3 voltage-free changeover contacts
Contact rating: 0.5 A
Housing (with connection box) W x H x D: 310 x 270 x 220 mm
Protection IP 55 (EN 60529)
Weight 4.5 kg

Features:

  • In situ measurement directly in the gas duct
  • Fast response
  • No gas treatment required
  • Easy to operate

 

alt